Live data

Each value says how often it is read and when it was last measured. The inverters, meters and battery are read every 5 minutes, the pyranometer every 10. The lab sends them to this site every 15 minutes, and after 30 minutes a value is marked as delayed.

  • Arrays 1 and 20 W
  • Vertical array0 W
  • Hydropower backup0 Wone way only
  • Battery84 W21 %, Giving power
  • Technical roomSunny Island and inverters
  • Lab appliances69 W
  • Car chargers6 W
LiveSolar now 0 W
Photo of the lab with its power flows drawn over it. The light moves the way the power goes, faster when more power flows. The backup comes from the campus grid, almost all hydropower in Norway, and the lab can only take from it. The battery and the inverters are inside the house. Measured
Solar power, total
The three arrays together, 4 770 Wp in total. A Sunny Boy shuts down when there is not enough light, and a sum with a missing term is not a smaller total, it is a wrong one. So this series has a hole whenever any inverter was asleep, which in Bergen means most of the winter afternoon.
0W
Read every 5 min, last
Global irradiance
Sunlight energy arriving on a horizontal surface.
0W/m²
Read every 10 min, last
Battery state of charge
How full the 14.4 kWh Tesvolt battery is.
21%
Read every 5 min, last
Consumption
The lab appliances and the charging stations together. The yellow sockets, which are wired directly to the HVL grid, are not part of it.
74W
Read every 5 min, last

Energy balance

What the lab uses, what the panels make, what the battery takes or gives, and what arrives through the backup feed from the grid. The consumption is measured by two meters, one on the lab appliances and one on the charging stations; the yellow sockets, wired straight to the HVL grid, pass through neither and are not counted. A negative battery value means the battery is being charged. The four numbers are read a few seconds apart, so a small difference is normal.
74WConsumptionequals0WSolar productionplus84WBatteryplus0WBackup from the grid

Measured

Today

  • Solar production (AC power of the three inverters together, W)
  • Sunlight (global irradiance on a horizontal surface, pyranometer, W/m²)
  • Battery (state of charge, %)
Solar production and sunlight todaySolar production today: highest 2.03 kW at 13:15, and up to 234 W/m² of sunlight.05001k1.5k2k2.5k05010015020025010:0013:0016:00wattswatts per square metresunrise 08:07sunset 16:36Solar productionSunlightnow

Solar production today: highest 2.03 kW at 13:15, and up to 234 W/m² of sunlight. The shaded stretches are night, from sunset to sunrise in Bergen. The same numbers are in the table view.
Battery level todayThe battery ran between 21 % and 28 % today, and is at 21 % now.02040608010010:0013:0016:00per centBatterynow

The battery ran between 21 % and 28 % today, and is at 21 % now.

Solar production

Read from each of the three inverters since 16 September 2026. An inverter switches off in low light, so early and late in the day an array can show no value.

Solar power, array 1 (monocrystalline)
6 monocrystalline panels Astronergy ASM6610M, 280 Wp each, 1 680 Wp, confirmed from the label on the back of a panel. Wired as one string of six in series since 28 March 2026. WHICH of the two tilted arrays this inverter is connected to is not confirmed: it comes from the lab wall chart, and two of the three inverters may have been exchanged about a year ago. The two tilted arrays cannot be told apart from their measurements, because six monocrystalline panels and six polycrystalline ones in series differ by three tenths of a volt.
0W
Read every 5 min, last
Solar power, array 2 (polycrystalline)
6 polycrystalline panels REC275PE, 275 Wp each, 1 650 Wp. Wired as one string of six in series since 28 March 2026. WHICH of the two tilted arrays this inverter is connected to is not confirmed, for the same reason as array 1: the assignment comes from the wall chart, and two inverters may have been exchanged since it was drawn.
0W
Read every 5 min, last
Solar power, array 3 (vertical, east and west)
Six frames standing vertically on the old railway rails, each carrying two MiaSole FLEX-02 120N thin film modules back to back, one facing east and one facing west. Twelve modules of 120 Wp, 1 440 Wp in total. The two faces are two strings of six wired in parallel, so the inverter reports them added together and can never tell east from west. These modules are not bifacial: a CIGS module is opaque and produces nothing through its back. It is the mounting that has two faces.
0W
Read every 5 min, last

No new reading since . The logger may be offline. System status.

Battery

Battery state of charge
How full the 14.4 kWh Tesvolt battery is.
21%
Read every 5 min, last
Battery power
Positive when the battery is supplying the lab, negative when it is being charged. Confirmed on 16 September 2026 by watching the state of charge rise from 28 % to 30 % while this value stayed negative.
84W
Read every 5 min, last

What the lab uses

The lab appliances and the two charging stations, each on its own meter, and their sum.

Consumption
The lab appliances and the charging stations together. The yellow sockets, which are wired directly to the HVL grid, are not part of it.
74W
Read every 5 min, last
Lab appliances
Everything the lab itself runs: the Raspberry Pi, the screen, the network switch, the router, the backup power supply. Measured by the meter marked "Lab local grid".
69W
Read every 5 min, last
Charging stations
The two car charging stations CC1 and CC2, measured at their own meter. It reads a few watts of standby when no car is plugged in.
6W
Read every 5 min, last

Backup from the grid

Starts when the battery falls below 20 % and stops at 25 %. From October to March the lab needs it regularly.

Backup from the grid
The lab is not connected to the grid for its normal supply, but a backup feed from the HVL grid can start when the battery falls below 20 %, and stops again at 25 %. This is what passes through it.
0W
Read every 5 min, last

Weather

Global irradiance
Sunlight energy arriving on a horizontal surface.
0W/m²
Read every 10 min, last
Outdoor temperature
Air temperature outside the lab, in the shade of the building. Measured on site, not taken from a forecast.
8.4°C
Read every 5 min, last
Temperature under the monocrystalline panels
Air temperature under the upper, monocrystalline row. In sunshine it runs well above the outdoor air, and a hotter cell produces less: this is the series to put against pv_power_array1.
6.1°C
Read every 5 min, last
Outdoor humidity
Relative humidity outside the lab.
81%
Read every 5 min, last

Inside the lab

Indoor temperature
Air temperature inside the lab. The sensor is close to a wall and to the ventilation outlet, so it reads the corner it sits in rather than the room; moving it is on the job list of autumn 2026.
20.0°C
Read every 5 min, last
Indoor humidity
Relative humidity inside the lab.
38%
Read every 5 min, last

Controlled loads

The lab switches these three loads itself, once a minute, from the battery level: the fuller the battery, the more it allows itself to run, and below 23 % it protects the battery and drops them. This page only shows their state. Nothing here can switch anything on or off.

Energy level
Control level EL0 to EL3, decided from the battery state of charge.
No data
Read every 5 min
Car charger CC1
Switched automatically by the battery state of charge.
Off
Read every 5 min, last
Second car socket CC2
Switched automatically by the battery state of charge.
Off
Read every 5 min, last
Heater, 2 kW
Switched automatically by the battery state of charge.
Off
Read every 5 min, last
Controlled loads, total
The three switched loads added together, as each Shelly reports them. It reads 0 W whenever the lab has turned them all off, which is normal below 65 % of battery.
0W
Read every 5 min, last
Power drawn by CC1
What the car charger actually draws, not only whether it is allowed to run.
0W
Read every 5 min, last
Power drawn by CC2
What the second car socket actually draws, not only whether it is allowed to run.
0W
Read every 5 min, last
Power drawn by the heater, 2 kW
What the heater actually draws, not only whether it is allowed to run.
0W
Read every 5 min, last
Explore the whole record

Any day, week, month or year, as a graph or a table, and downloadable as a CSV with its metadata.